2.14 LED Indicators
Troubleshooting the operation of the IEC Master port can be performed using
several methods.
The first and quickest is to scan the LEDs on the module to determine the
existence and possibly the cause of a problem. This section provides insight into
the operation of the Serial Port status LEDs. Information on the module’s other
LEDs can be found in the ProLinx Reference Guide.
2.14.1 LEDs for Port 0 Serial Port
Some ProLinx modules have three extra serial ports. Each of these serial ports
has two LEDs indicating status.
LED
Color
Description
Port 0 - ACT
Off
No activity on the port.
Green Flash
The port is either actively transmitting or receiving data
Port 0 - ERR
Off
Normal state. When off and Port Active led is indicating
activity, there are no communication errors
Red On or Flashing Activity on this led indicates some communication error
was detected, either during transmit or receive
2.14.2 LEDs for the PROFIBUS Slave Port
ACTIVE
ERROR
Description
Flashing
On
PROFIBUS communication problem (not
receiving output)
Off
On
Module configured and waiting for first output
data set.
Flashing
together
Configuration error during initialization.
Alternate
flashing
Watchdog timer expired.
On
Off
Normal operation.
On
Rapid/irregular flash
Configuration problem from master.
Off
Flashing
User timeout expired.
Off
Off
Module not receiving power or program
terminated.