ProSoft Technology 5105-103M-PDPS User Manual
Page 31

5105-103M-PDPS ♦ ProLinx Gateway
Start Here
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
User Manual
ProSoft Technology, Inc.
Page 31 of 144
November 24, 2010
1.7
103M Protocol Configuration
The following is excerpted from a configuration file showing typical examples
used for configuration of the 103M driver. A default configuration file for each
module application that includes the 103M interface card is available for
download from the www.prosoft-technology.com web site. This default
configuration can easily form the basis for a working solution. This file can either
be downloaded from the ProSoft web site at www.prosoft-technology.com, or
transferred from the module.
The configuration file contains the following topics:
[Section]
Description
[IEC-870-5-103 Master]
General configuration for the driver.
[IEC-870-5-103 Master Port n]
Configuration for one of the application ports.
[IEC-103 Master Session x]
Definition of each control unit.
[IEC-103 Master Session x Sector y] Definition for each sector in the controlled unit.
[IEC-103 Master Commands]
Command list to control slave units.
1.7.1 [IEC-103 Master Commands]
This section can contain up to 1000 user defined commands to be executed by
the module and sent to the controlled devices. There is no need to place Class 1
or Class 2 polls in this list for the controlled devices as the master driver for each
port will execute these automatically when the port is idle. In order for the port to
be idle, make sure that there is idle time available, and that the commands do not
constantly utilize the ports.