3.4.19 Generic functions in control direction
INF
Semantics
<240>
Read headings of all defined groups
<241>
Read values or attributes of all entries in one group
<243>
Read directory of a single entry
<244>
Read value or attribute of a single entry
<245>
General interrogation of generic data
<248>
Write entry
<249>
Write entry with confirmation
<250>
Write entry with execution
<251>
Write entry abort
3.4.20 Basic application functions
⌧
Test mode
⌧
Blocking of monitor direction
Disturbance data
Generic services
⌧
Private data (if ASDU type is supported by module)
3.4.21 Miscellaneous
Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in
7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No
different rating shall be used in ASDU 3 and ASDU 9, that is, for each
measurand there is only one choice.
Measurand Max. MVAL = rated value times
1,2
or
2,4
Current L
1
⌧
⌧
Current L
2
⌧
⌧
Current L
3
⌧
⌧
Voltage L
1-E
⌧
⌧
Voltage L
2-E
⌧
⌧
Voltage L
3-E
⌧
⌧
Active power P
⌧
⌧
Reactive power Q
⌧
⌧
Frequency f
⌧
⌧
Voltage L
1
- L
2
⌧
⌧