ProSoft Technology 5105-103M-PDPS User Manual
Page 41

5105-103M-PDPS ♦ ProLinx Gateway
Start Here
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
User Manual
ProSoft Technology, Inc.
Page 41 of 144
November 24, 2010
1.8
PDPS Protocol Configuration
The following illustration from ProSoft Configuration Builder shows the
PROFIBUS Slave configuration for a ProLinx PDPS module.
1.8.1 [PROFIBUS SLAVE]
The PROFIBUS Slave section contains the data that applies to the PROFIBUS
Slave parameters.
Slave Address
0 to 125
The parameter specifies the node address on the PROFIBUS network for the
slave emulated in the module. Each node on the network must have a unique
address.
Note: Although valid PROFIBUS Node addresses range from 0 to 125, Node 0 is not a valid node
number for a Slave module and that Nodes 0, 1, and 2 are usually reserved for PROFIBUS
Masters. Users are advised to use Node numbers 3-125
Swap Input Bytes
Yes or No
This parameter specifies if the data in the input data area of the module is to be
byte swapped. If the order of the bytes in the words stored in the database is not
correct, use this option. A value of Yes causes the module’s program to swap the
bytes in each word. A value of No indicates no byte swapping will occur.