ProSoft Technology 5105-103M-PDPS User Manual
Page 26

Start Here
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 26 of 144
ProSoft Technology, Inc.
November 24, 2010
For each point, configure the following values.
ASDU Type: ASDU type for the point
Function Type: Function type for the point
Point Index: Information number for the point
Database Index: The module database location where the value will be copied.
The type of addressing will depend on the ASDU type:
ASDU Type
DB Addressing
1
Bit address with each point occupying 2 bits
2
Bit address with each point occupying 2 bits
3
Word address with each point occupying 4 words
4
Double-word address for the single float value
5
Byte address with each point occupying 12 bytes
9
Word address with each point occupying 9 words
For example, to configure the following points,
Time-tagged message point with information number 17 (teleprotection
active) and distance protection function (128). The value will be copied to bits
0 and 1 in word 1 (second word) in the module database.
Measurands I point with information number 144 (measurands I) and
overcurrent protection function (160). The value will be copied to word 50 in
the module Database.