ProSoft Technology 5105-103M-PDPS User Manual
Page 108

Reference
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 108 of 144
ProSoft Technology, Inc.
November 24, 2010
TYPE 9: Measurands II
Bytes
Description
Spec
1
Value of 9
1
I = 1 to 9 for number of values
1
COT
1
Common address of ASDU
1
Function Type
1
Information number
2
Current L
1
7.2.6.8
2
Current L
2
7.2.6.8
2
Current L
3
7.2.6.8
2
Voltage L
1-E
7.2.6.8
2
Voltage L
2-E
7.2.6.8
2
Voltage L
3-E
7.2.6.8
2
Active power P
7.2.6.8
2
Reactive power Q
7.2.6.8
2
Frequency f
7.2.6.8
Value of I determines number of parameters passed in the message with a range
of 1 to 9 but always starts with the L
1
value.
Definition and Presentation of ASDUs in Control Direction
TYPE 6: Time synchronization
Bytes
Description
Spec
1
Value of 6
1
0x81
1
COT
1
Common address of ASDU
1
Function Type = GLB (255)
1
Information number
7
7-Octet binary time
7.2.6.29
TYPE 7: Initiation of general interrogation
Bytes
Description
Spec
1
Value of 7
1
0x81
1
COT
1
Common address of ASDU
1
Function Type = GLB (255)
1
Information number
1
SCN (scan number 0 to 255)
7.2.6.21