ProSoft Technology 5105-103M-PDPS User Manual
Page 126

Reference
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 126 of 144
ProSoft Technology, Inc.
November 24, 2010
3.4.3 Transmission speed
⌧
9 600 bit/s
⌧
19 200 bit/s
3.4.4 Link Layer
There are no choices for the link layer.
3.4.5 Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
3.4.6 Common Address of ASDU
⌧
One Common Address of ASDU (identical with station address)
⌧
More than one Common Address of ASDU
3.4.7 Selection of standard information numbers in monitor
direction
3.4.8 System functions in monitor direction
INF
Semantics
⌧
<0>
End of general interrogation
⌧
<0>
Time synchronization
⌧
<2>
Reset FCB
⌧
<3>
Reset CU
⌧
<4>
Start/restart
⌧
<5>
Power on