ProSoft Technology 5105-103M-PDPS User Manual
Page 115

5105-103M-PDPS ♦ ProLinx Gateway
Reference
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
User Manual
ProSoft Technology, Inc.
Page 115 of 144
November 24, 2010
Example Event Data Block From PLC
Start Byte
End Byte
Description
0
0
150 (Raw data write)
1
1
100 (Event data)
2
3
Start register in database for write
4
5
Number of registers to write (1 to 94)
6
7
Not Used
8
9
Not Used
10
197
Words to write to the database
198
198
Reserved
199
199
150 (Raw data write)
Example Response Block From GW
Start Byte
End Byte
Description
0
0
100 (Event data)
1
1
150 (Raw data write)
2
3
Event Count (0 to 9)
4
183
Event Data (0 to 9 event data structures)
184
197
Reserved for future use
198
198
Events in buffer (0 to 99)
199
199
100 (Event data)
Example Set Time Data Block From PLC
Start Byte
End Byte
Description
0
0
200 (Set Time)
1
1
201 (Get Time)
2
3
Year
4
5
Month
6
7
Day
8
9
Hour
10
11
Minutes
12
13
Seconds & milliseconds
14
198
Reserved for future use
199
199
200 (Set Time)