Rebooting the gateway – ProSoft Technology PLX81-EIP-61850 User Manual
Page 60

Diagnostics and Troubleshooting
PLX8x-EIP-61850 ♦ Communication Gateway
User Manual
Server to
IEC 61850 Client
Page 60 of 167
ProSoft Technology, Inc.
July 2, 2015
4.3.1 Status values
The Driver Status Register possible values are:
Value
Description
1
OK
0
Failed or Driver startup/restart is occurring
The 61850 IED status register possible values:
Value
Description
1
Node connected
0
Node initializing
-1
Node disconnected. It takes up to 15 minutes to display, and first shows
as “-2”.
-2
Node in error
4.4
Rebooting the Gateway
There are several ways to reboot the gateway.
Disconnect and reconnect power from the gateway.
From the PLC, write to the Reboot_Module tag. This causes the gateway to
reboot. Below shows the Reboot_Module tag in the EtherNet/IP Mapping
window in the ProSoft EIP-68150 Configuration Manager.
From the gateway webpage, use the Reboot Gateway feature. Refer to Web
Service and Gateway Web Page on page 72.
Note: The gateway reboots automatically after you download a new configuration
file to the gateway.