PLX8x-EIP-61850 ♦ Communication Gateway
Reference
Server to
IEC 61850 Client
User Manual
ProSoft Technology, Inc.
Page 109 of 167
July 2, 2015
5.6.2 IEC 61850 Benefits
Object-oriented data model
Introduces Logical Nodes (LNs) for formally defining functions (for example
XCBR = Circuit Breaker, XSWI = Isolator or earthing switch)
LN
defines standardized access to it’s data
Performance guidelines per LN strongly influence the communication system
structure
Communication technology based upon standardized rules, not rules stated
by chance by customer specifications
Strong formal description of automation system, which is key for specification,
design, and engineering
Self-describing (Example: vendor name plate information)
5.6.3 IEC 61850 Communication Features
Specific Communication Service Mapping (SCSM) is done via MMS (ISO/IEC
9506-1 and ISO/IEC 9506-2) and to ISO/IEC 8802-3. This is part IEC 61850-
8-1 of the standard.
Specific Communication Service Mapping (SCSM) for Sampled Values is
over ISO/IEC 8802-3. This is part IEC 61850-9-2 of the standard.
Ethernet has proven performance for the demands of IEC 61850. For best
performance, it is recommended that you use Ethernet switches, rather than
hubs.
5.6.4 SCL / Standardized Data Exchange
IEC
61850’s SCL (Substation Configuration Description Language) introduces a
powerful feature for substation automation. It provides a vendor-independent
representation of the su
bstation’s configuration. For example, XCBR is a circuit
breaker, no matter who the vendor is, what the country the vendor is from, what
country the system integrator is from, where the installation is.
IEC 61850 has a number of SCL-type files:
SSD for substation specification description
SCD for the substation configuration description
ICD for IED capability description (like a configuration template for the IED)
CID for the configured IED description
Note: This concept is key for meeting engineering challenges