2.17 Importing an Updated IED File
You may need to make changes to the CID, ICD, or SCD files after you create
the IED system configuration in the gateway. For example, you may need to
modify a DATA-SET, or add or remove some Data Attributes. When you make
changes like this, it’s easy to update the project in the ProSoft ProSoft 61850
Configuration Manager with the new information.
1 Right-mouse-click on the CID,
SCD,
OR
ICD filename you want to update in
the Device View section of ProSoft 61850 Configuration Manager and choose
U
PDATE
IED.
2 In the Open dialog box, browse to the directory containing the ICD, CID, or
SCD file. Often you use the exact same filename as when you first imported
the file into ProSoft EIP-61850 Configuration Manager.