Direct Control with Normal Security
Direct control with normal security is commonly used for operations that act on
local data (such as a LED test) or on data for which return information is not
supervised (for example switch on a heating). It uses the Operate and
TimeActivatedOperate services.
{This diagram and text has been taken directly from the IEC 61850 Standard
document.}
SBO (Select Before Operate) with Normal Security
SBO control with normal security first verifies that the Data Attribute is not
currently selected by a different Client; that it is operable; and that the operation
is not restricted. If this is verified, then the Operate request should proceed. It
uses these services:
S
ELECT
C
ANCEL
O
PERATE
T
IME
A
CTIVATED
O
PERATE
SBO with normal security Data Attributes are generally Controllable single point
(SPC) attribute types. These are things such as:
R
UN
D
IAGNOSTICS
T
RIGGER RECORDER
R
ESET RECORDER MEMORY
C
LEAR MEMORY