Adding the Gateway to RSLogix 5000
PLX8x-EIP-61850 ♦ Communication Gateway
User Manual
Server to
IEC 61850 Client
Page 50 of 167
ProSoft Technology, Inc.
July 2, 2015
3.4
Download the project to the processor to verify the connection
1 Save, and then download the project to the processor.
2 A yellow triangle in RSLogix 5000 means an error on connection. Check that
the Output size and Input size for the Class 1 connection in the gateway
configuration matches and the Comm Format is SINT. Try increasing RPI
time of module if the error persists.
3 If errors persist, re-download the configuration to make sure that the module
configuration matches the configured RSLogix 5000 program.
4 For additional troubleshooting, use the ProSoft EIP-61850 Configuration
Manager. Right-click the ProSoft Gateway bubble, and choose D
IAGNOSTIC
.
Class 1 displays the connection RPI time of processor and the IP address of
the ENBT. The open connection count starts at 1 and increments if the
connection to the processor is interrupted or there is a connection timeout.
State, open connection, and connection timeout are controlled by the code.
You can change the RPI and Ethernet IP in the ladder configuration in
RSLogix 5000 (right-click connection0 and choose P
ROPERTIES
).