When you right-click the IEC
61850 bubble representing that IED and choose
C
ONFIGURE
, the IEC 61850 Mapping Tool window shows the previously
configured tags. If any of the previously configured Data Attributes for that
IED are now missing from the new CID, SCD, or ICD file that you just
imported, then those tags are highlighted in red. This lets you know that they
are not in the updated IED file.
3 Right-click the missing tag and choose D
ELETE
. This removed the tag
mapping for the IED. Any corresponding mappings on the EtherNet/IP side
of the Gateway are also deleted.
4 When you have finished updating the mapping, choose M
APPING
>
S
AVE
to
save the changes.
5 Download the updated project to the gateway.