Grid Over Frequency
F32
Overfrequency on the grid side
Grid Under Frequency
F33
Underfrequency on the grid side
Grid CB Trip
F34
CB20 (grid circuit breaker) was tripped during operation
Parameters Version Error
F40
Version difference between the internal parameter table and the
program parameter table
Flash Memory Failure
F41
The flash memory used for programming the DSP C6000 on the
control board has failed.
FPGA Failure
F42
FPGA failure in XCU (main control) board
DSP28x Failure
F43
DSP F2000 on the control board has failed
ADC Failure
F44
The analog-digital converter on the control board has failed
NVSRAM Failure
F45
NVSRAM on the XCU (main control) board has failed.
ASYNC Failure
F46
ASYNC Warning (W31) has been repeated more than 10 times
CAN Failure
F47
CAN communication failure in the CAN network
MC22 Failure
F49
MC22 failed.
Emergency Stop
F50
The emergency stop (OFF switch) was pressed.
Cabinet Over Temp.
F51
Cabinet temperature > 55°C
MMI-XCU Communication Error
F63
Communication failure between MMI and XCU board
Table 32: Fault