KACO Powador XP200-HV TL User Manual
Page 58
User interface
Page 58
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Parameter
Unit
Range
Description
Factory settings
Asynchronous Fault
Count
–
0 ... 100
Reserved parameter
10
Asynchronous Fault
Enable
–
0 ... 1
Reserved parameter
0
Grid Positive
Sequence
0
999.9
Positive sequence value of grid
0
COSPHI Control
Mode
–
0 ... 5
Reactive power supply method in
internal mode and RPC mode
•
0: disabled
•
1: fixed P
•
2: fixed cosφ
•
3: fixed Q
•
4: cosφ(P/Pn)
•
5: Q(U)
0
COSPHI Internal
Power Factor
–
–0.999 ... 1
Power factor reference in internal
mode
1
COSPHI Internal
Reactive Power
%
–99.9 ... 99.9
Reactive power reference in internal
mode (percent for rated one)
0
COSPHI Actual
Power Factor
–
–0.999 ... 1
Actual power factor value that is
applied (read only)
1
COSPHI RPC Power
Factor
–
–0.999 ... 1
Power factor reference in RPC mode
1
COSPHI RPC Reac-
tive Power
%
–99.9 ... 99.9
Reactive power reference in RPC
mode (percent for rated one)
0
COSPHI Stray Ratio
–
0 ... 2
Setup value for COSPHI control
Device-specific
Positive Sequence
PLL Enable
–
On(1), Off(0)
Usage of grid voltage of positive
sequence at PLL
1
FRT K Factor
–
0 ... 10
Setup constant during FRT control
2
FRT IQ Ramp
ms
0 ... 99999
Time to change the current from 0 A
to rated current. This time determines
the slope of the active current after
grid fault detection.
4000
FRT IQ Ramp Time
ms
0 ... 99999
Total time that the FRT IQ ramp func-
tion is activated
2000
FRT Overcurrent
Protection Time
ms
0 ... 99999
Time that the inverter is stopped after
grid fault clearance
200
Positive Sequence
LPF
Hz
0 ... 100
Cut-off frequency for RMS value of
positive sequence
100
PLL Freq LPF
Hz
0 ... 100
Cut-off frequency for frequency value
detection of PLL
100
Q(V) Control Target
Voltage
V
208 ... 440
Value of Q(V) Control Target Voltage
Device-specific
Q(V) Control K
Factor
–
0 ... 50
Setup constant for voltage control of
BDEW
3.1