Parameter
Unit
Range
Description
Factory settings
Unbalanced Current
Limit
%
0 ... 100
Unbalanced current level
20
Cabinet FAN PWM
–
0 ... 100
Reserved parameter
100
Remote Power Con-
trol Ramp
s
0 ... 600
Slope of inverter output active poser
when remote power is controlled
10
Total Yield
kWh
0 ... 99999999
Total yield of generation (read only)
–
Today Yield
kWh
0 ... 99999999
Day yield of generation (read only)
–
IIVCD P Gain
–
0 ... 99999
P gain of inverter output voltage
controller D-axis for initial operation
voltage
0.2
IIVCQ I Gain
–
0 ... 99999
I gain of inverter output voltage
controller Q-axis for initial operation
voltage
5
Anti-Islanding
Enable
–
0 ... 99999
Usage of anti-islanding controller
•
0: no
•
1: yes
If the anti-islanding function is acti-
vated and a grid failure occurs, the
inverter automatically disconnects
itself from the power grid within a
few seconds.
If the anti-islanding function is not
activated, the inverter generates
power to load during grid failure.
0
APS Line Deadband
–
0 ... 99999
Setup value for anti-islanding control
0.11
Reactive Power
Limit
–
0 ... 99999
Setup value for anti-islanding control
0.06
Wind Speed
–
0 ... 99999
Reserved parameter
–
Power Derating
Enable
–
0 ... 1
Usage of power decline controller
according to PEBB temperature
•
0: no
•
1: yes
0
Power Derating
Enable Temperature
–
50 ... 100
Temperature level which starts
decreasing power according to PEBB
temperature
70
Power Derating
Disable Tempera-
ture
–
40 ... 90
Temperature level which stops
decreasing power according to PEBB
temperature
50
Power Derating
Reference Tempe-
rature
–
45 ... 95
PEBB temperature reference value
60
Power Derating P
Gain
–
0 ... 10
P gain of power declining controller
according to PEBB temperature
2
Grid IIR Filter Cutoff
Frequency
Hz
0 ... 10
Filter cut-off frequency used for RMS
value detection of grid voltage
1.5