3 temperature dependent power derating, 4 configuring the e-mail server, Temperature dependent power derating – KACO Powador XP200-HV TL User Manual
Page 70: Configuring the e-mail server
Configuration
Page 70
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
9.3
Temperature dependent power derating
T1
76
°C
kW
T
T
70
60
50
160
200
136
200
250
170
0
0
kW
T
0
T2
T3
PEBB temperature
Output power
Power derating active
Active output power:
P(kW) = 200 – (T
PEBB
– 60) • 4
Active output power:
P(kW) = 250 – (T
PEBB
– 60) • 5
XP250-HV
XP200-HV
Figure 67: Power derating examples
The diagrams show examples for power derating.
The depicted temperature ranges have the following
meaning:
T1:
The inverter produces energy and the PEBB tem-
perature rises.
T2:
When the PEBB temperature is higher than 70%,
the power derating is activated.
The inverter controls the output power accor-
ding to the equations given in the diagrams until
the power derating is deactivated.
T3:
The output power decreases and the PEBB tem-
perature drops.
When the PEBB temperature is lower than 50%,
the power derating is deactivated.
The inverter does not decrease the output
power.
9.4 Configuring the e-mail server
The e-mail server is used to transmit general data (PV power, grid power, PV voltage, PV current, PV temperature)
periodically to the Powador Web or to other e-mail addresses configured by the user.
E-mail server parameters
The following parameters have to be set for configuration ():
Parameter
Description
Powador Web Individual Server
Enable
Enable/disable e-mail function
Interval
Set the transmission interval
SMTP IP Address
Address of the e-mail server
–
SMTP Username
E-mail account at the e-mail server
–
SMTP Password
Password for the e-mail account
–
Plant Name
Optional name for the inverter
Serial Number
Specific serial number for the inverter
Sender Address
Sender e-mail address
–
Receiver Address
Receiver e-mail address
–
Table 28: E-mail server parameters