KACO Powador XP200-HV TL User Manual
Page 80
Maintenance/Cleaning
Page 80
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Recommended
maintenance intervals
Maintenance work
6 months*
Cleaning or replacement
Filter mats in the air intake filters
Cleaning
Inside of the cabinet
Fans
6 months
Function check
Emergency stop (OFF)
12 months*
Cleaning
Power section of the heat sink
12 months
Visual inspection
Contact connections
Fuses
Switches
Overvoltage protection
Redundant auxiliary power supplies
Check all parts in the cabinet for
–
Heavy dust deposits and soiling
–
Moisture (especially water that has permea-
ted from the outside)
Visual inspection (and
replacement, if necessary)
All warning labels
Function check
Fans
Door contacts
Operating lights and fault lights
*If heavy soiling is present at the installation location, you may need to shorten the maintenance interval.
Table 30: Maintenance intervals