2 mechanical data, Mechanical data – KACO Powador XP200-HV TL User Manual
Page 12
Technical data
Page 12
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
4.2
Mechanical data
XP200-HV TL
XP250-HV TL
XP350-HV TL
Display
TFT LCD touchscreen
Interfaces
RS485/Ethernet/USB
4 x analogue inputs
1 x digital input
1 x S0 input
1 x digital output
1 x S0 output
Memory [GB]
SD card, up to 8
Operating temperature range [°C]
–20 ... +50 full rated power, no derating
Storage temperature range [°C]
–20 ... +70
Relative humidity [%]
0 ... 95
Cooling [m³/h]
•
part A
•
part B
Fan, max. 4040
max. 2840
max. 1200
Fan, max. 4040
max. 2840
max. 1200
Fan, max. 5460
max. 4260
max. 1200
Protection rating
IP 21 (in accordance with DIN EN 60529:2000)
Intended for indoor use only in accordance with
IEC 62103:2003
Noise emission [dB (A)]
< 70
Housing
Upright, steel housing
H x W x D [mm]
2120 x 2400 x 870
Base [mm]
2400 x 840
Total weight [kg]
1170
1200
1370
Table 2:
Mechanical data of the inverter