8 network parameters, 9 recording parameters – KACO Powador XP200-HV TL User Manual
Page 60
User interface
Page 60
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Parameter
Unit
Range
Description
Factory settings
COSPHI_9
–
–0.999 ... –0.95
and 0.95 ... 1
Variable power factor reference accor-
ding to active power P_9.
1
P_9
%
0 ... 100
Active power setup conference for
COSPHI_9.
50
COSPHI_10
–
–0.999 ... –0.95
and 0.95 ... 1
Variable power factor reference accor-
ding to active power P_10.
1
P_10
%
0 ... 100
Active power setup conference for
COSPHI_10.
50
Table 23: Controller parameters
8.5.8 Network parameters
Parameter
Unit
Range
Description
Factory settings
Configuration
–
0 ... 10
0: DHCP
1: Static
1
IP
–
IP address (format: xxx.xxx.xxx.xxx)
1
Netmask
–
The subnet mask used for the network
(format: 255.255.255.0)
0
Gateway
–
Router address (format: xxx.xxx.xxx.xxx)
1
Table 24: Network parameters
8.5.9 Recording parameters
Parameter
Unit
Range
Description
Factory settings
Recording interval minute
10 ... 60
Time period for the recording of parameters
10
Grid power
–
ON (1)
OFF (0)
If deactivated, the grid power is not recorded.
ON (1)
PV power
–
ON (1)
OFF (0)
If deactivated, the PV power is not recorded.
ON (1)
PV voltage
–
ON (1)
OFF (0)
If deactivated, the PV voltage is not recorded.
ON (1)
PV current
–
ON (1)
OFF (0)
If deactivated, the PV current is not recorded.
ON (1)
PV temperature
–
ON (1)
OFF (0)
If deactivated, the PV temperature is not
recorded.
ON (1)
Irradiation
–
ON (1)
OFF (0)
If deactivated, the irradiation (insolation)
is not recorded.
ON (1)
Statistics reset
–
–
All statistical data is reset.
–
Table 25: Recording parameters