4 technical data, 1 electrical data, Technical data – KACO Powador XP200-HV TL User Manual
Page 11: Electrical data, 4technical data
Technical data
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Page 11
4
Technical data
4.1
Electrical data
Input levels
XP200-HV TL
XP250-HV TL
XP350-HV TL
Max. PV generator power [kW]
240
300
420
MPPT range [V]
450 ... 830
No-load voltage [V]
1000*
Monitoring of input voltage [V]
Stand-by from V
on
> 300
Night shutdown from V
off
< 250
MPP starting voltage V
start
> 600
Voltage ripple [%]
< 3
Current ripple [%]
< 4
Max. input current [A]
467
611
856
Output levels
XP200-HV TL
XP250-HV TL
XP350-HV TL
Rated power [kW]
200
250
350
Max. power [kW]
200
250
350
Line voltage
In accordance with country-specific guidelines
Output voltage [V]
290 (±10%)
Rated current [A]
398
498
697
Max. current [A]
398
498
697
Rated frequency [Hz]
50/60
cos phi
0.80 inductive ... 0.80 capacitive
Distortion factor [%]
< 3 at rated power
Fault signal relay
Potential-free NO contact, max. 30 V/1 A
S0 output
Open collector output, max. 30 V/50 mA
General electrical data
XP200-HV TL
XP250-HV TL
XP350-HV TL
Max. efficiency [%]
98.2
98.1
98.3
European efficiency [%]
97.8
97.8
98.0
Internal consumption in
standby mode [W]
< 80
Internal consumption in operation [W]
< 360
Min. grid feed power [W]
10 000
Grid monitoring
In accordance with country-specific guidelines
CE conformity
yes
Table 1:
Electrical data of the inverter
*
To protect the hardware, the inverter starts up only at voltages <950 V