KACO Powador XP200-HV TL User Manual
Page 30
Installation
Page 30
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Electrician
"
A terminating resistor (120 Ω, 0.5 W, 1 %) is installed on the main control board (XCU).
For termination disposal use a jumper between RS485 A1 (1a) and RS485 C1 (2b).
Signal transceiver
-RS485
GND
A(DATA–)
Jumper
B(DATA+)
1b 2b 3b 4b
1a 2a 3a 4a
Figure 25: RS485-1 termination disposal
NOTE
Terminating resistors need to be installed at both ends of the device within the communication
railroad.