5 parameters, 1 pvarray parameters, 2 inverter parameters – KACO Powador XP200-HV TL User Manual
Page 52
User interface
Page 52
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
8.5
Parameters
8.5.1 PvArray parameters
Parameter
Unit
Range
Description
Factory settings
MPPT Enable
–
On(1), Off(0)
“On” represents that MPPT is opera-
ting
1
MPPT V Maximum
V DC
0 ... 900
Maximum voltage to run MPPT
830
MPPT V Start
V DC
450 ... 800
MPPT wake-up voltage
600
MPPT T Start
s
0 ... 600
Time delay for MPPT wake-up
Device-specific
MPPT P Stop
W
0 ... 10000
MPPT power point to begin sleep test
timer
Device-specific
MPPT T Stop
s
0 ... 3600
Time delay for MPPT sleep test
Device-specific
MPPT V Minimum
V DC
200 ... 800
Minimum voltage to run MPPT
410
DC Over Voltage
Level
V DC
300 ... 950
Upper limit for PV over voltage fault
Device-specific
DC Over Current
Level
%
0 ... 150
Upper limit for PV over current fault
130
MPP Factor
–
0 ... 1
Maximum power point factor
0.8
MPP Range Upper
V DC
10 ... 300
Upper limit of maximum power point
80
MPP Range Lower
V DC
10 ... 300
Lower limit of maximum power point
80
PV Operation Level
V DC
900 ... 950
Maximum PV operation level
Device-specific
Table 17: PvArray parameters
8.5.2 Inverter parameters
Parameter
Unit
Range
Description
Factory settings
Inverter Transfor-
mer
–
Yes(1), No(0)
“Yes” represents that inverter trans-
former is operating
Device-specific
Inverter Capacity
kW
100 ... 500
Power value that inverter can deal
with
Device-specific
Inverter Over Cur-
rent Level
%
0 ... 200
Upper limit for inverter over current
fault
130
Current Limit
%
0 ... 150
Limit of current which enters to the
inverter
100
Cabinet Temp.
Maximum
°C
30 ... 70
Upper limit for cabinet over tempera-
ture warning
55
Cabinet Temp.
Minimum
°C
–25 ... 10
Lower limit for cabinet under tempe-
rature warning
–15
Table 18: Inverter parameters