Medium voltage guideline
DE
MSp.
Country-specific functions
The functions and paramaters described in this section are set to comply with the BDEW Medium
Voltage Directive (“Mittelspannungsrichtlinie”). They are activated for inverters that are operated
with “Germany” as the country setting and “Medium Voltage Directive” as the grid type.
If the “Medium Voltage Directive” is selected as the grid type the MMI displays a warning message when the user
attempts to change the default settings used to comply with the BDEW Medium Voltage Directive.
Grid
Rated Grid Voltage (V)
Rated Grid Frequency (Hz)
Grid OV Level 1 (%)
Grid UV Level 1 (%)
Grid OF Level 1 (Hz)
0
0
0
0
0.0
Set
Set
Set
Set
Set
back
1
5
This parameter changes the
FRT settings for the
Medium Voltage Directive.
Do you really want to change it?
Yes
No
Figure 65: Message warning against violation of the Medium Voltage Directive (example)
9.2.1 Configuring the cosphi control
Cosphi control
The cosphi control function is for controlling active and reactive power which is infused from the inverter to the grid
with Powador-proLOG, MMI, and XCU at long distance.
Communication between components
Cosphi control enables remote control of reactive and active power by setting the reference of reactive and active
power.
Communication between cosphi components:
•
User activates cosphi control by Powador-proLOG.
•
Powador-proLOG sends a cosphi control massage at two-minute intervals.
•
MMI interprets the cosphi control message from Powador-proLOG to modify parameters of XCU.
•
XCU operates according to the modified parameter by MMI.
•
Cosphi (limited to Fixed cosphi and Fixed Q) has two overlapping parameters for RPC and internal modes.
MMI modifies the parameter for RPC mode only.
If the relative RPC mode parameter remains longer than five minutes unmodified, XCU will operate according to
the parameter for internal mode.
Cosphi control ways
Cosphi control operates with five reactive and active power control ways according to COSPHI Control Mode para-
meter setting.
Power
control
Description
Relative
parameters
Fixed P
Control the maximum active power with Remote Power Control
parameter value (% of max. rated power).
•
Remote Power Control