4 date and time parameters, 5 digital interface parameters – KACO Powador XP200-HV TL User Manual
Page 54
User interface
Page 54
Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN
Parameter
Unit
Range
Description
Factory settings
Grid Under Voltage
Level 2 Trip time
ms
40 ... 2000
Time for grid under voltage level 2
trip
100
Grid Under
Frequency Level 1
Trip time
ms
1000 ... 20000
Time for grid under frequency level
1 trip
10000
Grid Under
Frequency Level 2
Trip time
ms
40 ... 2000
Time for grid under frequency level
2 trip
100
Grid Over
Frequency Level 1
Trip time
ms
40 ... 2000
Time for grid over frequency level 1
trip
100
FRT Enable
–
On(1), Off(0)
“On” means that FRT is working
0
Grid Over Voltage
FRT Enable
–
On(1), Off(0)
“On” means that the grid overvoltage
FRT is working
0
Power Reduction
Gradient Level
%/Hz
0.0 ... 100
Gradient level for frequency-depen-
dant power reduction
40
Power Reduction
Deactivation
Frequency
Hz
0.0 ... 0.3
Frequency limit for power reduction
deactivation
0.05
Grid Over
Frequency Level 2
Hz
0.0 ... 3.0
Upper limit for grid over frequency
level 2
1.5
Grid Over
Frequency Level 2
Trip time
ms
40 ... 2000
Time for grid over frequency level 2
trip
100
Table 19: Grid parameters
8.5.4 Date and time parameters
Parameter
Unit
Range
Description
Factory settings
Year
–
2000 ... 3000
Current year
–
Month
–
1 ... 12
Current month
–
Day
–
1 ... 31
Current day
–
Hour
–
0 ... 23
Current hour
–
Minute
–
0 ... 59
Current minute
–
Second
–
0 ... 59
Current second
–
Table 20: Parameters for date/time
8.5.5 Digital interface parameters
Parameter
Unit
Range
Description
Factory settings
DI1 select
–
0 ... 20
Selection for digital input 1
0
DO1 select
–
0 ... 20
Selection for digital output 1
0