Parameter

Unit

Range

Description

Factory settings

Grid Under Voltage

Level 2 Trip time

ms

40 ... 2000

Time for grid under voltage level 2

trip

100

Grid Under

Frequency Level 1

Trip time

ms

1000 ... 20000

Time for grid under frequency level

1 trip

10000

Grid Under

Frequency Level 2

Trip time

ms

40 ... 2000

Time for grid under frequency level

2 trip

100

Grid Over

Frequency Level 1

Trip time

ms

40 ... 2000

Time for grid over frequency level 1

trip

100

FRT Enable

On(1), Off(0)

“On” means that FRT is working

0

Grid Over Voltage

FRT Enable

On(1), Off(0)

“On” means that the grid overvoltage

FRT is working

0

Power Reduction

Gradient Level

%/Hz

0.0 ... 100

Gradient level for frequency-depen-

dant power reduction

40

Power Reduction

Deactivation

Frequency

Hz

0.0 ... 0.3

Frequency limit for power reduction

deactivation

0.05

Grid Over

Frequency Level 2

Hz

0.0 ... 3.0

Upper limit for grid over frequency

level 2

1.5

Grid Over

Frequency Level 2

Trip time

ms

40 ... 2000

Time for grid over frequency level 2

trip

100

Table 19: Grid parameters

8.5.4 Date and time parameters

Parameter

Unit

Range

Description

Factory settings

Year

2000 ... 3000

Current year

Month

1 ... 12

Current month

Day

1 ... 31

Current day

Hour

0 ... 23

Current hour

Minute

0 ... 59

Current minute

Second

0 ... 59

Current second

Table 20: Parameters for date/time

8.5.5 Digital interface parameters

Parameter

Unit

Range

Description

Factory settings

DI1 select

0 ... 20

Selection for digital input 1

0

DO1 select

0 ... 20

Selection for digital output 1

0