VS-616PS5 Programming Manual

87

Selects whether a fault contact output is activated during automatic restart.

A setting of “0” will energize the fault relay only after the number of restart attempts as
programmed in parameter L5-01 has been exhausted.

A setting of “1” will energize the fault relay upon every fault. Thus, the fault contact
will energize and then de-energize as the restart procedure is occurring.

L5-02 Automatic Restart Operation Selection

B

Setting

Description

0

No fault relay (factory default).

1

Fault relay is active.

Section L: Protection Parameters

L5 Fault Reset