Coast to Stop with Timer 1 (B1-03 = “3”)

Upon removal of the run command, a new run command is blocked until the coast to
stop timer has elapsed (same as Decel 1). After the timer elapses, the user must
enter another run command for the inverter to begin acceleration. This stopping
method is disabled during flux vector control.

Setting Range:

0 to 1

Factory Default:

0

A “reverse run disabled” setting does not allow a reverse run command from the con-
trol circuit terminal or the digital operator. This setting is used in applications where a
reverse run command is undesirable.

Select an operation mode to be used when the speed reference (analog input) drops
below the minimum speed setting (El -08).

B1-04 Reverse Operation Enable/Disable

B

Setting

Description

0

Reverse run is enabled (factory default).

1

Reverse run is disabled.

B1-05 Operation Selection at Zero Speed

A

Setting

Description

0

E1-08 is ignored, run according to speed reference.

Output Frequency

Coasting

Decel Time 1
(C1-02)

Accel Time 1
(C1-01)

Time

ON

ON

ON

FWD (REV)
Run Command

Run Command Disabled

Figure 4 Stopping Method - Coast to Stop w/Timer

Section B: Application Parameters

B1 Sequence