Yaskawa VS-616PS5 Series Programming Manual User Manual
Page 12

12
VS-616PS5 Programming Manual
•
Coast to Stop with Timer 1 (B1-03 = “3”)
Upon removal of the run command, a new run command is blocked until the coast to
stop timer has elapsed (same as Decel 1). After the timer elapses, the user must
enter another run command for the inverter to begin acceleration. This stopping
method is disabled during flux vector control.
Setting Range:
0 to 1
Factory Default:
0
A “reverse run disabled” setting does not allow a reverse run command from the con-
trol circuit terminal or the digital operator. This setting is used in applications where a
reverse run command is undesirable.
Select an operation mode to be used when the speed reference (analog input) drops
below the minimum speed setting (El -08).
B1-04 Reverse Operation Enable/Disable
B
Setting
Description
0
Reverse run is enabled (factory default).
1
Reverse run is disabled.
B1-05 Operation Selection at Zero Speed
A
Setting
Description
0
E1-08 is ignored, run according to speed reference.
Output Frequency
Coasting
Decel Time 1
(C1-02)
Accel Time 1
(C1-01)
Time
ON
ON
ON
FWD (REV)
Run Command
Run Command Disabled
Figure 4 Stopping Method - Coast to Stop w/Timer
Section B: Application Parameters
B1 Sequence