L8-03 Stopping method selection after OH pre-alarm

0: Ramp to stop

2: Fast-stop

1: Coast to stop

3: Alarm only

-

0~3

3

A

L8-05 Input phase loss protection

0: Disabled

1: Enabled

-

0/1

0

A

L8-07 Output phase loss protection

0: Disabled

1: Enabled

-

0/1

0

A

L8-10 Ground fault protection selection

0: Disabled

1: Enabled

-

0/1

1

A

O

Operator Parameters

O1

Monitor Selection

O1-01 Analog output Channel 1 selection

5: Motor speed

6: Output voltage

7: DC bus voltage

8: Output power

9: Torque reference (internal)

15: External terminal 13 input voltage

16: External terminal 14 input voltage

17: External terminal 16 input voltage

18: Motor secondary current (I

q

)

19: Motor excitation current (I

d

)

20: Primary speed after SFS

21: Speed controller ASR input

22: Speed controller ASR output

27: q Axis current control reference

28: d Axis current control reference

29: Voltage limit control output

30: q Axis current control output

31: d Axis current control output

32: Output voltage reference (V

q

)

33: Output voltage reference (V

d

)

45: External torque reference

46: Torque compensation value

49: Control section software number

50: Speed detection PG counter value

53: PID feedback

54: DI-16H input status

-

5~53

6

B

O1-02 Monitor selection after power-up

1: Speed reference

3: Output current

2: Output speed

4: User monitor

1

1~4

1

B

O1-03 Scale for setting and monitoring frequency

-

0~39999

1

B

O2

Key Selection

O2-01 Local/remote key

0: Disabled

1: Enabled

-

0/1

1

B

O2-02 STOP key during external terminal operation

0: Disabled

1: Enabled

-

0/1

0

B

O2-04 Inverter model selection

-

00~FF

kVA dependent

B

O2-05 Digital operator M.O.P. mode selection

0: Disabled

1: Enabled

-

0/1

0

A

O2-06 Digital operator disconnection detection

0: Disabled

1: Enabled

-

0/1

0

A

O2-07 Operation time setting

H

0~65535

0

A

No.

Parameter Description

Unit

Setting Range

Default

Access

Level

User

Setting

Appendix