Yaskawa VS-616PS5 Series Programming Manual User Manual
Page 111

VS-616PS5 Programming Manual
111
L8-03 Stopping method selection after OH pre-alarm
0: Ramp to stop
2: Fast-stop
1: Coast to stop
3: Alarm only
-
0~3
3
A
L8-05 Input phase loss protection
0: Disabled
1: Enabled
-
0/1
0
A
L8-07 Output phase loss protection
0: Disabled
1: Enabled
-
0/1
0
A
L8-10 Ground fault protection selection
0: Disabled
1: Enabled
-
0/1
1
A
O
Operator Parameters
O1
Monitor Selection
O1-01 Analog output Channel 1 selection
5: Motor speed
6: Output voltage
7: DC bus voltage
8: Output power
9: Torque reference (internal)
15: External terminal 13 input voltage
16: External terminal 14 input voltage
17: External terminal 16 input voltage
18: Motor secondary current (I
q
)
19: Motor excitation current (I
d
)
20: Primary speed after SFS
21: Speed controller ASR input
22: Speed controller ASR output
27: q Axis current control reference
28: d Axis current control reference
29: Voltage limit control output
30: q Axis current control output
31: d Axis current control output
32: Output voltage reference (V
q
)
33: Output voltage reference (V
d
)
45: External torque reference
46: Torque compensation value
49: Control section software number
50: Speed detection PG counter value
53: PID feedback
54: DI-16H input status
-
5~53
6
B
O1-02 Monitor selection after power-up
1: Speed reference
3: Output current
2: Output speed
4: User monitor
1
1~4
1
B
O1-03 Scale for setting and monitoring frequency
-
0~39999
1
B
O2
Key Selection
O2-01 Local/remote key
0: Disabled
1: Enabled
-
0/1
1
B
O2-02 STOP key during external terminal operation
0: Disabled
1: Enabled
-
0/1
0
B
O2-04 Inverter model selection
-
00~FF
kVA dependent
B
O2-05 Digital operator M.O.P. mode selection
0: Disabled
1: Enabled
-
0/1
0
A
O2-06 Digital operator disconnection detection
0: Disabled
1: Enabled
-
0/1
0
A
O2-07 Operation time setting
H
0~65535
0
A
No.
Parameter Description
Unit
Setting Range
Default
Access
Level
User
Setting
Appendix
VS-616PS5 Parameter List