Yaskawa VS-616PS5 Series Programming Manual User Manual
Page 79

VS-616PS5 Programming Manual
79
Setting Range:
±109.2%
Factory Default:
0.0%
Sets the terminal 21 output bias for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-02, then add the
bias value set in H4-03.
Selects the analog output monitors for terminal 23 (see Terminal 21 Analog Output
Selection). The resolution of terminal 23 is 9 bits plus a sign bit.
Setting Range:
±300.0%
Factory Default:
1.0
Sets the terminal 23 output gain for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-05, (see Figure 48).
Setting Range:
±109.2%
Factory Default:
0.0%
Sets the terminal 23 output bias for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-05, then add the
bias value set in H4-06, (see Figure 48).
Selects the type of voltage signal output at terminals 21 and 23.
H4-03 Terminal 21 Analog Output Bias
B
H4-04 Terminal 23 Analog Output Selection
B
H4-05
Terminal 23 Analog Output
Gain
B
H4-06 Terminal 23 Analog Output Bias
B
H4-07
Analog Output Signal Selection
B
Setting
Description
0
0 to 10V output (factory default)
1
±10V output
Figure 48 Analog Output Gain and Bias Adjustment
+10
-10
0
Bias (%)
0
Reference (%)
2.50
Gain
1.00
Section H: Control Circuit Terminal Parameters
H4 Analog Outputs