VS-616PS5 Programming Manual

Section H: Control Circuit Terminal Parameters

H2 Digital Outputs

Closes when run command is input from the digital operator.

• Overtorque Detection 1 - N.O. (setting: “B”)

Closes during overtorque detection 1 (L6-01, see section L6, Overtorque Detec-
tion
).

• Loss of Speed Reference (setting: “C”)

Closes when the speed reference is reduced by 90% within 400ms. The inverter
will respond according to the setting of reference loss selection (L4-05). After refer-
ence loss, if L4-05 = “1,” then operation continues at 80% of the previous speed ref-
erence, and the contact closes.

Dynamic Braking Resistor Overheat (setting: “D”)

Closes during braking resistor overheating or a braking transistor fault.

Fault (setting: “E”)

Closes when a fault occurs (except CPF00 and CPF01).

Alarm (setting: “10”)

Closes while an alarm is displayed.

• Fault Reset (setting: “11”)

Closes while a fault is being reset.

• Timer Output (setting: “12”)

Closes when a timer contact input closes (after On-delay time elapses).
Opens when a timer contact input opens (after Off-delay time elapses).

• Speed Agree 2 (setting: “13”)

Closes whenever the output speed “agrees” with the Speed reference plus or minus
the Speed Agree Detection Width (L4-04). This is used for setting up an alternate
detection width.

Fwd Run Command

Master Speed Reference

Output Speed

Reference Loss Contact

ON

OFF

80% Frequency

80%

10%

OFF

ON

OFF

ON

OFF

400ms

400ms

Figure 41 Reference Loss Timing Diagram