VS-616PS5 Programming Manual

F4

AO-08/AO-12 Set-up

Setting Range:

1 to 53

Factory Default:

5

Selects the analog output monitors for channel 1 of the AO-08 and AO-12 options.
Possible settings are as follows:

F4-01 Analog Output Channel 1 Selection

A

Setting

Description

1

Speed reference

2

Output frequency

3

Inverter output current

5

Motor speed (factory default)

6

Output voltage

7

DC bus voltage

8

Output power

9

Torque reference (internal)

15

External terminal 13 input voltage

16

External terminal 14 input voltage

17

External terminal 16 input voltage

18

Motor secondary current (Iq)

19

Motor excitation current (Id)

20

Primary frequency after SFS

21

Speed controller ASR input

22

Speed controller ASR output

27

qAxis current control reference

28

dAxis current control reference

29

Voltage limit control output

30

qAxis current control output

31

dAxis current control output

32

Output voltage reference (V

q

)

33

Output voltage reference (V

d

)

45

External torque reference

46

Torque compensation value

49

Control section software number

50

Speed detection PG counter value

53

PID feedback

Section F: Option Parameters

F4 AO-08/AO-12 Set-up