beautypg.com

Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 16

background image

16

VS-616PS5 Programming Manual

Setting Range:

0.0 to 5.0s

Factory Default:

1.0s

This parameter sets the time to allow the rotor to pull in (align) with the magnetic field
at initial excitation. Pull-in waiting time is set in units of 0.1s.
The current vs. time plot during the magnetic pull-in process is as follows:

B3-05 Magnetic Pull-in Time

A

Operation Status

B3-02 Adjustment

B3-04 Adjustment

B3-05Adjustment

Slow Start

-

Decrease set value

Decrease set value

Insufficient torque, and

“STO” is output

Increase set value.

-

-

Current Value

0

1

2

Time

B3-04

B3-05

B3-02

Section B: Application Parameters

B3 Magnetic Pull-in