52

VS-616PS5 Programming Manual

F2

AI-14B Set-up

Sets CH1 to CH3 input functions when AI-14B option is connected.

When the 3CH individual input selection is used, set parameter B1-01 to “1” (fre-
quency reference from control circuit terminal). The option/inverter reference selec-
tion, which is selected by a multi-function contact input (H1-XX = “2”), is disabled
when using the AI-14B option.

F2-01 AI-14B Function Selection

A

Setting

Function

CH1 (TC1 to TC4)

CH2 (TC2 to TC4)

CH3 (TC3 to TC4)

0

3-channel individual

input (factory default)

Substitute for

terminals 13 & 17

Substitute for

terminals 14 & 17

Substitute for

terminals 16 & 17

1

3-channel additional

input

Sum of CH1 to CH3 input values is used as the speed

reference value. (Reference the AI-14B instruction manual for

details).

Section F: Option Parameters

F2 AI-14B Set-up