VS-616PS5 Programming Manual

• Overtorque Detection 1 - N.C. (setting: “17”)

Opens during overtorque detection 1 (L6-01, see section L6, Overtorque Detec-
tion
, on page 81).

• Overtorque Detection 2 - N.O. (setting: “18”)

Closes during overtorque detection 2 (L6-01, see section L6, Overtorque Detec-
tion
, on page 81).

• Overtorque Detection 2 - N.C. (setting: “19”)

Opens during overtorque detection 2 (L6-01, see section L6, Overtorque Detec-
tion
, on page 81).

• During Reverse Run (setting: “1A”)

Closes during a reverse run command.

• Baseblock 2 - N.C. (setting: “1B”)

Opens when the inverter output shuts OFF.

• Monitoring/Regenerating Mode (setting: “1D”)

Closes during regenerative operation.

• Automatic Restart (setting: “1E”)

Closes during automatic restart operation.

• OL1 Pre-alarm (setting: “1F”)

Closes when the motor-calculated electronic thermal overload value increases to
90% of the internal fault detection level.

• OH Pre-alarm (setting: “20”)

Closes when the heatsink temperature exceeds the Overheat Temperature Level
(L8-02), or when a multi-function contact input (H1-XX = “B”) closes.

Detection Width 1 (L4-04)

Output Speed

Frequency

ON

Detection Level 1 (L4-03)

Figure 45 Speed Detection 2 Signal Timing Diagram

Detection 4 Signal

OFF

OFF

Section H: Control Circuit Terminal Parameters

H2 Digital Outputs