VS-616PS5 Programming Manual

59

F9

CP-916 Setup

This parameter selects the initial state for an external fault condition when the inverter
is configured for serial communication using the CP-916.

This parameter selects the condition of detection for an external fault when using the
CP-916 option.

Setting this parameter selects the stopping method when an EFO fault is detected.

This parameter sets the # of scans per each trace sample when using the CP-916B
option card.

Setting Range:

0-6000

Factory Default:

0

Note: Setting F9-04 to zero executes a trace every scan.

F9-01 External Fault Input Level from Communication Option

A

Set Value

Description

0

Detection by N. O. (when closed, the inverter will trip), (factory default).

1

Detection by N. C. (when open, the inverter will trip).

F9-02 External Fault Detection Selection from Communication Option

A

Set Value

Description

0

The fault will always be detected, even when the drive is stopped (factory default).

1

The fault will be detected only when the drive is running.

F9-03 Operation at External Fault Input from Communication

Option

A

Set Value

Description

0

Ramp to stop according to C1-02 set value.

1

Coast to stop (factory default).

2

Ramp to stop according to C1-09 set value.

3

Alarm flashes, operation continues.

F9-04 Trace Sampling of Option

A

Section F: Option Parameters

F9 CP-916 Set-up