Yaskawa VS-616PS5 Series Programming Manual User Manual
Page 59

VS-616PS5 Programming Manual
59
F9
CP-916 Setup
This parameter selects the initial state for an external fault condition when the inverter
is configured for serial communication using the CP-916.
This parameter selects the condition of detection for an external fault when using the
CP-916 option.
Setting this parameter selects the stopping method when an EFO fault is detected.
This parameter sets the # of scans per each trace sample when using the CP-916B
option card.
Setting Range:
0-6000
Factory Default:
0
Note: Setting F9-04 to zero executes a trace every scan.
F9-01 External Fault Input Level from Communication Option
A
Set Value
Description
0
Detection by N. O. (when closed, the inverter will trip), (factory default).
1
Detection by N. C. (when open, the inverter will trip).
F9-02 External Fault Detection Selection from Communication Option
A
Set Value
Description
0
The fault will always be detected, even when the drive is stopped (factory default).
1
The fault will be detected only when the drive is running.
F9-03 Operation at External Fault Input from Communication
Option
A
Set Value
Description
0
Ramp to stop according to C1-02 set value.
1
Coast to stop (factory default).
2
Ramp to stop according to C1-09 set value.
3
Alarm flashes, operation continues.
F9-04 Trace Sampling of Option
A
Section F: Option Parameters
F9 CP-916 Set-up