VS-616PS5 Programming Manual
35
D
Reference Parameters
D1
Preset References
Setting Range:
0.00 to 100.00%
Factory Default:
0.00%
Up to 9 preset speed references (including jog) with the multi-function contact input
function selections. When using the multi-step speed references, set the reference
selection (B1-01) to “0,” and set terminal 16 selection (H3-05) to “1F.” See the follow-
ing table for programming preset speed references.
Setting Range:
0.00 to 100.00%
Factory Default:
10.00%
The jog frequency reference can be set in this parameter. Depress the JOG key on
the digital operator, or close terminal 7 to use this function. The jog command always
has priority over other reference commands. When using the multi-step speed refer-
ences as indicated in the table above, change the jog command from terminal 7 to
terminal 8 (H1-06 = “6”). Selecting the jog frequency reference via a multifunction
input selects the jog frequency reference only. A separate run command also needs
to be applied to start the unit.
D1-01 Preset Reference 1
Q
D1-02 Preset Reference 2
Q
D1-03 Preset Reference 3
Q
D1-04 Preset Reference 4
Q
D1-05 Preset Reference 5
B
D1-06 Preset Reference 6
B
D1-07 Preset Reference 7
B
D1-08 Preset Reference 8
B
Terminal 5
H1-03 = “3”
Terminal 6
H1-04 = “4”
Terminal 7
H1-05 = “5”
Terminal 8
H1-06 = “6”
Speed Reference
Open
Open
Open
Open
Speed Reference 1 - Set Reference Source
(B1-01) to “0.”
Closed
Open
Open
Open
Speed Reference 2 - Set Terminal 16 Selection
(H3-05) to “1F.”
Open
Closed
Open
Open
Speed Reference 3
Closed
Closed
Open
Open
Speed Reference 4
Open
Open
Closed
Open
Speed Reference 5
Closed
Open
Closed
Open
Speed Reference 6
Open
Closed
Closed
Open
Speed Reference 7
Closed
Closed
Closed
Open
Speed Reference 8
Closed
Closed
Closed
Closed
Jog Speed Reference
D1-09 Jog Frequency Reference
B
Section D: Reference Parameters
D1 Preset References