Option Parameters

F1

PG Option Set-up
These parameters set up the Speed feedback pulse generator (PG).

Setting Range:

0 to 10000

Factory Default:

30

This parameter sets the number of PG pulses per motor revolution (pulses/rev). Enter
the PPR of the hall sensor signals HS4 & HS5 for Hall sensor only feedback (F8-
01=1).
Use the encoder PPR for motors using encoders (F8-01=0). Consult the fac-
tory when using encoders with greater than 4096 PPR.

Selects the stopping method when a disconnected PG is detected.

Selects the stopping method when an overspeed condition is detected.

Selects the stopping method when excessive speed deviation is detected.

F1-01 PG Pulses per Revolution

Q

F1-02 PG Disconnection Detection Stopping Method

B

Setting

Description

0

Ramp to stop - according to C1-02. (Declaration time 1).

1

Coast to stop (factory default).

2

Fast-stop - according to C1-09.

3

Alarm flashes, operation continues.

F1-03 Overspeed Detection Stopping Method

B

Setting

Description

0

Ramp to stop - according to C1-02 (Declaration time 1).

1

Coast to stop (factory default).

2

Fast-stop - according to C1-09.

3

Alarm flashes, operation continues.

F1-04 PG Deviation Detection Stopping Method

B

Setting

Description

0

Ramp to stop - according to C1-02 (Declaration time 1).

1

Coast to stop.

2

Fast-stop - according to C1-09.

3

Alarm flashes, operation continues (factory default).

Section F: Option Parameters

F1 PG Option Set-up