SMA STP 8000TL-10 User Manual
Page 83

SMA Solar Technology AG
11 Messages
Installation Manual
STP8-17TL-IA-en-31
83
9003
< Grid param. locked >
The current country data set is locked.
• Enter a valid SMA Grid Guard code
for changing the country data set.
9005
< Changing grid param. not possible >
< Ensure DC supply >
• DC voltage at the DC input is not
sufficient to run the main CPU.
• The selected rotary switch setting for
the language settings is not
programmed.
• The parameters to be changed are
protected.
• Ensure that sufficient DC voltage is
available (green LED glowing or
flashing).
• Check the setting of the rotary
switches (see Section 5.4.2).
• Enter the SMA Grid Guard code.
9007
< Abort self-test >
There is either an error in the AC
installation or the configured voltage and
frequency limits do not comply with the
requirements of the Italian electricity grids.
• Check AC installation.
• Eliminate connection error
(see Section 6.3 "Connecting the
Electricity Grid (AC)", page 29).
• Check that the country setting is
correct (see Section 6.5 "Setting the
Country Standard and Display
Language", page 45).
The self-test is only required for
installations in Italy.
Event no. Display message and cause
Corrective measures