14  Technical Data

SMA Solar Technology AG

102

STP8-17TL-IA-en-31

Installation Manual

AC Output

* Depending on country setting

Rated power at 230 V, 50 Hz

10,000 W

Maximum apparent AC power

10,000 VA

Rated grid voltage

3/N/PE, 230 V/400 V

AC voltage range*

160 V … 280 V

Nominal AC current at 230 V

14.5 A

Maximum output current

16.0 A

Maximum short-circuit current

0.05 kA

Total harmonic factor of output current at
AC voltage < 2%
and AC power > 0.5% of nominal AC power

≤ 3%

Maximum residual output current

96 mA

Rated power frequency

50 Hz

AC power frequency*

50 Hz/60 Hz

Operating range at AC power frequency 50 Hz

44 Hz … 55 Hz

Operating range at AC power frequency 60 Hz

54 Hz … 65 Hz

Displacement power factor, adjustable

0.8

overexcited

… 0.8

underexcited

Feed-in phases

3

Connection phases

3

Overvoltage category as per IEC 60664-1

III