6430

< Relay control defective input X >
X stands for the affected input. The relay
control at the affected input is defective.

Contact the SMA Service Line
(see Section 16 "Contact", page 126)

6432

< HSS-IGBT defective input X >
HSS-IGBT cannot be switched on or off.

Contact the SMA Service Line
(see Section 16 "Contact", page 126)

6439

< Varistor monitoring defective >
The varistor monitoring is defective.

Contact the SMA Service Line
(see Section 16 "Contact", page 126)

6501,
6502,
6509

< Self diagnosis > or
< Overtemperature >
The inverter switches off due to excessive
temperature.

• Ensure sufficient ventilation.
• Check heat dissipation

(see Section 10.2 "Checking Heat
Dissipation", page 67).

6603,
6604

< Self diagnosis > or
< Overload >

• Contact the SMA Service Line

(see Section 16 "Contact",
page 126)

6701,
6702

< Comm. disturbed >
A fault has occurred in the internal
communication of the inverter. However,
the inverter continues feeding into the grid.

If this event occurs frequently:

• Contact the SMA Service Line

(see Section 16 "Contact",
page 126)

6801,
6802

< Self-diagnosis > or
< Input A defective >

• Contact the SMA Service Line

(see Section 16 "Contact",
page 126)

6901,
6902

< Self-diagnosis > or
< Input B defective >

• Contact the SMA Service Line

(see Section 16 "Contact",
page 126)

7001,
7002,
7007

< Sensor fault fan permanently on >
Overtemperature in the inverter or sensor
defective.

• Contact the SMA Service Line

(see Section 16 "Contact",
page 126)

7101

< SD card defective >

Re-format the SD card.

• Cancel write protection on SD card.
• Re-save the files to the SD card.

7102

< Parameter file not found or defective >

• Copy the parameter file into the SD

card drive :\PARASET directory.

7105

< Param. setting failed >

• Check whether the parameters of

the SD card are valid.

• Ensure change rights via

SMA Grid Guard code.