6  Electrical Connection

SMA Solar Technology AG

56

STP8-17TL-IA-en-31

Installation Manual

– The surge arrester marked "PE 500" must be

inserted in the bottom slot.

– If surge arresters are only required for input A,

the two surge arresters must be mounted on the
two upper slots.

– If input B is also to be protected, surge arresters

must be plugged into all slots.

– A green strip in the window (A) indicates that

the surge arrester is fully functional. A red strip
in the window indicates that the surge arrester is
faulty. In this case, a warning also appears in
the display with the event number "83".

5. Dock the DC lid at an angle, and attach. The

captive screws must protrude.