6  Electrical Connection

Installation Manual

STP8-17TL-IA-en-31

31

6.3.2 AC Connection Procedure

1. Check the line voltage and compare it with the permissible voltage range (see Section 14

"Technical Data", page 95).

2. Disconnect the miniature circuit-breaker from all three phases and secure against reconnection.
3. Release all 6 captive screws of the lower enclosure

lid.

4. To remove the lower enclosure lid, lift it from the

bottom.

5. Check that the country setting of the inverter is correct using the supplementary sheet provided

with the default settings.

Damage to the inverter by use of screw-type fuses as switch-disconnectors
A screw-type fuse, e.g. DIAZED fuse or NEOZED fuse, is not a switch-disconnector and thus
may not be used as a load disconnection unit. A screw-type fuse only acts as cable protection.
If the inverter is disconnected under load using a screw-type fuse, the inverter may be damaged.

• Use only a switch-disconnector or a miniature circuit-breaker as a load disconnection unit.