9  Disconnecting the Inverter from Voltage Sources

Installation Manual

STP8-17TL-IA-en-31

65

7. Use a suitable multimeter to verify the absence of

voltage for L1, L2 and L3 to N at the AC terminal.
The maximum diameter of the test probe is 2 mm.
☑ If voltage is present, check the installation.

8. Verify the absence of voltage in L1, L2 and L3

against PE at the AC terminal.
☑ If voltage is present, check the installation.

9. Verify the absence of voltage in the multi-function

relay against PE at all terminals.
☑ If voltage is present, check the installation.

PE