SMA STP 8000TL-10 User Manual
Page 79

SMA Solar Technology AG
11 Messages
Installation Manual
STP8-17TL-IA-en-31
79
4003
< String X defect. >
< Check generator >
The "X" stands for the affected string. This
string polarity is either reversed or the
string has failed. Further strings may also
be affected. The PV array is not short
circuited.
• Disconnect the inverter
(see Section 9 "Disconnecting the
Inverter from Voltage Sources",
page 63).
• Check the design and the circuitry of
the PV array (see Section 6.4.1
"Conditions for DC Connection",
page 34).
• Check whether the same voltage is
present at the strings inputs
A1 to A5.
• If not, one of the PV modules is
possibly defective.
4005
< Part.str. X low p. >
< Check generator >
The "X" stands for the affected substring
The string monitoring has either failed or
detected a weak substring.
• Check the part string indicated.
6001 …
6009,
6101 …
6112,
6201 …
6203,
6301,
6304 …
6306,
6401 …
6411,
6415,
6416,
6422,
6433,
6437,
6438
< Self diagnosis > or
< Interference device >
• Contact the SMA Service Line
(see Section 16 "Contact",
page 126)
6429
< ESS Relay fault Input X >
X stands for the affected input. The ESS
relay or ESS-IGBT cannot be switched on
or off.
Contact the SMA Service Line
(see Section 16 "Contact", page 126)
Event no. Display message and cause
Corrective measures