6  Electrical Connection

Installation Manual

STP8-17TL-IA-en-31

43

6. Follow the same procedure to connect all further

strings.
It is no longer necessary to wait 60 seconds.

7. Ensure that all DC connectors are securely in place.

The Sunny Tripower starts
beeping.

The Sunny Tripower short-circuits the PV array.

On no account disconnect the Electronic Solar Switch or

the DC connectors. Wait until the Sunny Tripower stops
beeping (after dark).
Pulling the DC connectors causes a risk of arcing, since the
Sunny Tripower short-circuits the PV array in order to
prevent reverse currents through individual strings.
Depending on the level of irradiation, this could trigger
current flows. However, the PV array and the
Sunny Tripower are in a safe state.

• Before leaving the Sunny Tripower, install a contact

barrier (e.g., fence) and moisture protection
(e.g., tarpaulin).

• Wait until dark before pulling out the Electronic Solar Switch

and all DC connectors, and only then eliminate any errors
(reversed pole or defective string).

The display is showing the
error message 40, 64 or
82.

• Follow the instructions on the display (see Section 11.2

"Error messages", page 74).

Number of Strings - Sunny Tripower 8000TL / 1000TL / 12000TL

The Sunny Tripower 8000TL / 10000TL / 12000TL have only 4 strings at input A.

Event

Measure