SMA STP 8000TL-10 User Manual
Page 76

11 Messages
SMA Solar Technology AG
76
STP8-17TL-IA-en-31
Installation Manual
701
< Frq. not permitted >
< Check parameter >
The power frequency is outside the
permissible range. The inverter
disconnects from the electricity grid for
safety reasons.
• As far as possible, check the power
frequency and observe how often
major fluctuations occur.
If there are frequent fluctuations and this
error occurs as a result, ask your network
operator if it would be acceptable to
change the operating parameters.
Discuss the proposed parameters with the
SMA Service Line.
1302
< Waiting for grid voltage > or
< Installation failure grid connection >
< Check grid and fuses >
The inverter has detected an error in the
AC cabling and cannot connect to the
electricity grid. The reason for this could be
an incorrect country setting.
• Check AC installation
• Eliminate connection error
(see Section 6.3 "Connecting the
Electricity Grid (AC)", page 29).
• Check that the country setting is
correct:
– Via rotary switch
(see Section 6.5.1 "Checking the
Country Standard", page 47)
– Via communication: set the
parameter "CntrySet" or "Set
country standard"
1501
< Reconnection fault grid >
The measured voltage or frequency is too
high or too low for connection to the
electricity grid.
Possibly, a changed country data set or
changed parameters do not correspond to
the local requirements for connecting to
the electricity grid.
• Check that the country setting is
correct:
– Via rotary switch
(see Section 6.5.1 "Checking the
Country Standard", page 47)
– Via communication: set the
parameter "CntrySet" or "Set
country standard"
• Check whether the voltage and
frequency of the electricity grid are
within the limits of the configured
country data set.
• If individual parameters within a
country data set have been
changed, re-select the original
country data set for the country of
installation.
Event no. Display message and cause
Corrective measures