SMA STP 8000TL-10 User Manual
Page 35

SMA Solar Technology AG
6 Electrical Connection
Installation Manual
STP8-17TL-IA-en-31
35
• The following thresholds at the DC input of the inverter must not be exceeded:
Use of Y adaptors for the parallel connection of strings
Y adaptors must not be visible or freely accessible in close proximity to the inverter.
• The DC electric circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter (see Section 9 "Disconnecting the
Inverter from Voltage Sources", page 63).
Sunny
Tripower
Maximum input voltage
(DC)
Maximum input current
(MPP) (DC)
Maximum short-circuit
current per string input
(DC)
Input area A/B
A1 … A5 / B
8000TL
1,000 V
22.0 A / 11.0 A
33 A / 12.5 A
10000TL
1,000 V
22.0 A / 11.0 A
33 A / 12.5 A
12000TL
1,000 V
22.0 A / 11.0 A
33 A / 12.5 A
15000TL
1,000 V
33.0 A / 11.0 A
40 A / 12.5 A
17000TL
1,000 V
33.0 A / 11.0 A
40 A / 12.5 A
Risk of fire as a result of overcurrent on the string input
Destruction of the inverter
Since the electronic string fuse shorts the PV array in the event of a fault, the thresholds for the
maximum short-circuit current per string input given in the table above must not be exceeded.
If a string input is overloaded, it can result in an electric arc and hence a risk of fire.
• Make sure that the thresholds specified in the table above are not exceeded.
• Check whether the short-circuit currents of the connected PV modules are in compliance with
the thresholds given in the table above.