SMA CLUSTER CONTROLLER Installation User Manual
Page 86

Design
Potential-free relay contacts
Maximum switching power
30 W
Maximum voltage load
48 V
DC
Maximum cable length
30 m (98 ft)
Analog Inputs
Number of analog inputs for current signals
3
Number of analog inputs for voltage signals
1
Internal resistance
450 Ω
Measurement range for current signals
0 mA to 20 mA
Measurement range for voltage signals
0 V to +10 V
Typical tolerance
± 0.3%
Maximum tolerance
± 2%
Maximum cable length
30 m (98 ft)
Analog outputs
Number of analog outputs for current signals
3
Measurement range for current signals
4 mA to 20 mA
Maximum tolerance
± 0.5%
Maximum cable length
3,000 m (9,842 ft)
Temperature Inputs
Quantity
2
Measuring shunt
Platinum sensor Pt100, platinum sensor Pt1000
Type of measurement
Two-conductor connection technology, four-con-
ductor connection technology
Measurement range
−40°C to +85°C (−40°F to +185°F)
Maximum tolerance*
± 0.5°C (± 0.9°F)
Maximum cable length*
20 m (65 ft)
* when measured with four-conductor connection technology
USB Ports
Quantity
2
Specification
USB 2.0 Hi‑Speed
9 Technical Data
SMA Solar Technology AG / SMA America, LLC
Installation Manual
ClusterController-IA-en-14
86