beautypg.com

SMA CLUSTER CONTROLLER Installation User Manual

Page 86

background image

Design

Potential-free relay contacts

Maximum switching power

30 W

Maximum voltage load

48 V

DC

Maximum cable length

30 m (98 ft)

Analog Inputs

Number of analog inputs for current signals

3

Number of analog inputs for voltage signals

1

Internal resistance

450 Ω

Measurement range for current signals

0 mA to 20 mA

Measurement range for voltage signals

0 V to +10 V

Typical tolerance

± 0.3%

Maximum tolerance

± 2%

Maximum cable length

30 m (98 ft)

Analog outputs

Number of analog outputs for current signals

3

Measurement range for current signals

4 mA to 20 mA

Maximum tolerance

± 0.5%

Maximum cable length

3,000 m (9,842 ft)

Temperature Inputs

Quantity

2

Measuring shunt

Platinum sensor Pt100, platinum sensor Pt1000

Type of measurement

Two-conductor connection technology, four-con-
ductor connection technology

Measurement range

−40°C to +85°C (−40°F to +185°F)

Maximum tolerance*

± 0.5°C (± 0.9°F)

Maximum cable length*

20 m (65 ft)

* when measured with four-conductor connection technology

USB Ports

Quantity

2

Specification

USB 2.0 Hi‑Speed

9 Technical Data

SMA Solar Technology AG / SMA America, LLC

Installation Manual

ClusterController-IA-en-14

86