Connection

Cable requirements

Temperature Inputs
(connection cable)

☐ Number of insulated conductors for tolerance ± 2°C (±3.6°F):

at least two

☐ Number of insulated conductors for tolerance ± 0.5°C

(±0.9°F): at least four

☐ Conductor cross-section: at least 4 x 0.25 mm

2

(at

least 4 x 24 AWG)

☐ External cable diameter: 4.5 mm to 7.0 mm (0.18 in to

0.28 in)

☐ Maximum cable length for four-conductor connection

technology: 20 m (65 ft)

☐ Maximum cable length for two-conductor connection

technology: 2.5 m (8 ft)

Inverter
(Speedwire)

☐ Number of insulated conductor pairs and conductor cross-

section: at least 2 x 2 x 0.22 mm

2

(at least 2 x 2 x 24 AWG)

☐ External diameter: the maximum external diameter depends on

the size of the cable gland or the conduit (see the installation
manual of the Speedwire/Webconnect interface).

☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP

or higher

☐ Plug type: RJ45 of Cat5, Cat5e, Cat6, Cat6a

Cat7 plugs cannot be used.

☐ Cable length between two nodes: max. 50 m (164 ft) with

patch cable, max. 100 m (328 ft) with installation cable

LAN

☐ Number of insulated conductor pairs and conductor cross-

section: at least 2 x 2 x 0.22 mm

2

(at least 2 x 2 x 24 AWG)

☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP

or higher

☐ Plug type: RJ45 of Cat5, Cat5e, Cat6, Cat6a

Cat7 plugs cannot be used.

☐ Cable length between two nodes: max. 50 m (164 ft) with

patch cable, max. 100 m (328 ft) with installation cable

6 Connection and Commissioning

SMA Solar Technology AG / SMA America, LLC

Installation Manual

ClusterController-IA-en-14